Air - Blast Circuit Breakers: Types, Advantages, Disadvantages, Application
Air – Blast Circuit Breakers
Air - Blast circuit breakers
employ high pressure Air – Blast as an arc quenching medium. The contacts are opened in a high flow of air blast established by the opening blast valve. The air blast cools the arc and sweeps away the arcing products to the atmosphere. It rapidly increases the dielectric strength of the medium between contacts and then prevents from re-establishing the arc. Consequently, the arc is extinguished and the flow of current is also interrupted.
Advantages of Air – Blast Circuit Breakers
The air – blast circuit breaker’s advantages are given below:
(i) The risk of fire is eliminated.
(ii) The growth of dielectric strength is so rapid that final contact needed a very small gap for arc extinction. It reduces the size of the device.
(iii) The arcing time is very small due to the quick build-up of dielectric strength between both contacts. That’s why, the arc energy is only a fraction of that in oil circuit breakers, thus resulting in less burning of contacts.
(iv) Cause of lesser arc energy, the air-blast circuit breakers are very suitable for conditions where frequent operations are required.
(v) The energy supplied for the arc extinction is gained from high-pressure air and is independent of the current interruption.
(vi) Short and consistent arc duration.
(vii) The burning of contacts is less due to less arc energy (since the arc duration is short and consistent).
(viii) Less maintenance is required.
(ix) High-speed operation.
(x) The facility of high-speed reclosure.
Disadvantages of Air – Blast Circuit Breaker
The disadvantages of air – blast circuit breaker are given below :
(i) The air has many properties one is the relatively inferior arc extinguishing property.
(ii) The air-blast circuit breakers are very sensitive circuit breakers than others to the variations in the rate of rise of restriking voltage.
(iii) Maintenance is required for the circuit breaker for compressor plant which supplies the air-blast.
(iv) The air leakage at the pipeline fittings create problems.
(v) Current chopping.
Applications of Air – Circuit Breaker
The air blast circuit breakers are using wide applications in high voltage installations. The majority of these circuit breakers for voltages up to 110 kV are of this type.
Types of Air – Blast Circuit Breakers
The classification of air – blast circuit breakers are
depending upon the direction of air-blast in relation to the arc,
(i)
Axial – blast type
In which the arc – blast is directed along the arc path.
(ii)
Cross – blast type
In this air – blast is directed at right angles to the arc path.
(iii)
Radial – blast type
In this type of circuit breaker air – blast is directed radially.
(i)
Axial – Blast Air Circuit Breaker
The figure shows the essential components of a typical
Axial-Blast Air Circuit Breaker
. The fixed and moving contacts of the circuit breaker are held in the closed position by spring pressure under normal conditions. The air reservoir of the circuit breaker is connected to the arcing chamber through an air valve. This valve remains closed during normal conditions but when the fault occurs on the system it opens automatically by the tripping.
When a fault occurs, the tripping impulse causes opening of the air valve which connects the air reservoir to the arcing chamber. The high-pressure air entering the arcing chamber which pushes away the moving contact against the spring pressure. The moving contacts are separated and an arc is struck between them. At the same time, the high-pressure air blast flows along the arc and takes away the ionized gases along with it. Consequently, the arc is extinguished and interrupted the flow of the current.It should be noted that in these types of circuit breakers, the contact separation required for interruption is generally small almost (
1-75
cm or so). These small gaps may constitute inadequate clearance for the normal service voltage. Cause of that, an isolating switch is incorporated as a part of such a circuit breaker. After the fault interruption, this switch opens immediately to provide the necessary clearance for insulation.
(ii)
Cross – Blast Air Circuit Breaker
In the cross – blast air circuit breaker, an air-blast is directed at right angles (90
o
) to the arc. The cross-blast lengthens and forces the arc into a suitable escarpment for arc extinction. The below Figure shows the essential parts of a typical cross-blast air circuit breaker. When the moving contacts are withdrawn, an arc is struck between both fixed and moving contacts. The high contact pressure cross-blast forces the arc into a chute consisting of arc splitters and baffles. The splitters help to increase the length of the arc and baffles provide improved cooling. The result is that the arc is extinguished and the current flow is interrupted. Because the air blast pressure is similar for all currents, the inefficiency at low currents is eliminated. The final gap for interruption is great enough to give normal insulation clearance therefore, a series isolating switch is not necessary.
SOURCE: https://www.chloshikhe.in/2020/06/air-blast-circuit-breakers.html













