The large-scale medical equipment electricity deepens and designs discussing simply
Went through 2 years to complete using at last in the building of the centre of tumour of Chinese People's Liberation Army General Hospital, it is China and even the Asian most advanced tumour rescue center at present, bilaminar 15 layers of 35,000 square meters in floor area and monosomatous inside on the ground in the underground, there are 26 full-length medical equipments ' Cyclotron, it is faulted accelerator, DSA, PET/CT, DR, thermotherapies high-frequency, simulation last machine, behind install,etc.) ,Among them 10 apparatuses are China's first introduction, the main design that electric and specialized as this project, each set apparatus following cooperating with numerous international apparatus producers, exchange, designing, confirming, designing, publishing picture step that be constructed, cooperated, debugged again, course though the hardships, learn a lot of things, see an apparatus which connects one comes into operation smoothly, handle patients and serve the scene of the society, that kind of feeling is unable to speak tables. Hope oneself in cooperate, deepen some technology in the the design, reap and make some summaries, for counterparts to consult.
The electric designing requirement of the large-scale medical equipment, will have a difference because the manufacturer is different, the key designed still lies in and the apparatus producer's professional engineer one is socialised, the correct understanding of the English materials, installation procedure and operation principle of the genuine understanding apparatus. Describe as follows on technological focal point and difficult point in the design as follows.
The main engine must be furnished with the specialized on-the-spot distribution box, this distribution box and on/off switch (EAT) linking up with it And emergency cock (AT) Must install before installation in place. Ancillary equipment and other electricity consumption facilities are (such as illumination, air conditioner) Power should offer by public electric wire netting of the hospital, be can install on the scene in distribution box controlled switch and protective circuit of themmed, but does not allow the on-the-spot distribution box to supply power for it absolutely.
The following is a circuit theory of the return circuit that the inner host computer of distribution box of tumour centre DSA apparatus supplies power:
The systematic power accords with the national norm, voltage 380V, maximum deviation can't exceed 10%. Frequency 50Hz, maximum deviation can't exceed 0.5Hz. The maximum deviation among the voltage between phases can't exceed 2% of the minimum phase voltage. The apparatus maximum power is 171KVA, serial power 20KVA, power factor 0.9; Apparatus crest current 289A twinkling of an eye such as maximum, continuous current 31A, can adopt circuit breaker rated current empty to turn on to go on protecting for 160A. The individual line of facility request supplies power. The three-phase line introduces the switch board with PE thread together after indicating phase sequence. Entering the wire cable must adopt the multiwire copper core wire, insert the circuit breaker that the rated current is 160A in the cupboard, and cable color and circuit breaker specification must accord with the regulation of the standard electrical installation manual. The switch board must possess and defend uncapping and locking the function, so as to ensure the demand of electric safe operation. The switch board emergency power off button needs to install on the wall by operating an operating desk of China, it is convenient for operating personnel to cut off the systematic power while the contingency takes place.
Second, systematic power supply cable
Preferably dispose the specialized power cable from voltage transformer to scene distribution box, and must be the copper core cable. Forbidden to insert the inductive load of high-power on this power cable, such as the air conditioner, the lift, the refrigerator,etc., in order to avoid the interference caused at the time of the start-stop of apparatus. In order to guarantee the resistance-value in line of power accords with the requirement in the above table, must follow actual construction length, one's own inner resistance-value of inner resistance-value and on-the-spot distribution box of the voltage transformer Ausgang of the cable, calculate the minimum sectional area of the cable spread, lay the length the longer, the Ausgang of the voltage transformer and inner resistance-value of the on-the-spot distribution box are the higher, the cable sectional area requires that the greater. The cable sectional area is chosen according to the formula computing of the following experience:
Cable sectional area A =(2* lays the length) /(56* cables of one's own resistance-values) .
Give an example: Measure in fact: It is 100m that the cable lays the length actually, is the inner resistance-value of the Ausgang of the voltage transformer 0.060 kilohms? ,The autogenous inner resistance-value of the on-the-spot distribution box is 0.030 kilohms.
So: One's own maximum of the cable allows the resistance-value =0.11-0.06-0.03 =0.02? . Cable sectional area A =( 2* 100) /( 56* 0.02) =178.5,So the cable sectional area should be 185mm2 at least.
Third, illumination are required
Preferably systematic form combined with adjustable incandescent lighting by the invariable fluorescent lamp illumination, in order to satisfy the patient's comfort and facilitate the operation of staff members. Take centre DSA of tumour as examples as follows, propose adopting the following lighting schemes:
Fourth, adopt and share grounded system and equipotential connection
Designing earlier stage, producer will demand to earth the apparatus alone, we should not be interpreted as this apparatus on the earth lead which earthes the steel plate this connect other apparatuses, so as not to interfere with. But not make the ground electrode alone. Not when we meet some producer stubborn requirements to make the ground electrode alone, do not adopt us to share and earth, I should analyze the explanation from the following aspects.
1. International standard IEC61312- 1. U.S.A.'s electric regulation (NEC) . China lightning protection normal ' 6.3.3 piece and 6.3.4 pair) Stipulate, adopt, share grounded system with equipotential to connect.
2. Adopting the inner electronic device of BLDG which is sharing the grounded system, it is difficult to set up earthing alone. Because of the outer cover of apparatus, the hardware of the whole BLDG, stiffening ribs, electricity guard ground systems insert and share the grounded system. If want to draw from the electronic device alone (function) The outdoor single ground electrode that the earth lead reaches, and it is difficult to totally isolate with the above-mentioned share grounded system in order to avoid striking back the voltage.
3. The single specialized earth lead is in high frequency (the operating frequency of the information apparatus) Under the situation, impedance is very large, so it is pointless to require the resistance to be small. Because in the impedance infinity of specialized earth lead from the syntony condition, disconnect in other words, become an aerial, make the apparatus accept the undesired signal instead.
4. Earth and unfavorable to voltage protection alone.
5. Needn't be afraid in cases TN-S is systematic the noise disturbance electronic device of the power-frequency current (PE and N separate, PE electric current of the without) at ordinary times . In more places of electronic device, should adopt the steel tube and close the steel raceway wired cable, in order to prevent short circuit current relatively multi-place of single phase earthing from flowing through to share the grounded system, cause the interference on electronic device.
So in the engineering, continue to use the old standard to require to some foreign countries and Chinese manufacturer the earthy method should be corrected alone. The above to design experience exchangement of about large-scale the intersection of medical equipment and electric promotion of computer lab, if there is not complete enough, please propose making a comment!
Bibliographical reference
2. Apparatus materials that the medical equipment Division of U.S.A. GE Company offers
3.IEC60364-7-710 INTERNATIONAL STANDARD