How I Troubleshoot an Air Conditioner 2-Stage Compressor (Solenoid)

tannertan36
AnasAbdin
🪼
"I'm Dorothy Gale from Kansas"

shark vs the universe

祝日 / Permanent Vacation
let's talk about Bridgerton tea, my ask is open

PR's Tumblrdome

Kaledo Art
I'd rather be in outer space 🛸

oozey mess
h
occasionally subtle
Monterey Bay Aquarium
Peter Solarz
we're not kids anymore.

izzy's playlists!

Discoholic 🪩
todays bird
$LAYYYTER
seen from Sri Lanka
seen from Türkiye
seen from India
seen from Canada
seen from Italy

seen from United States

seen from Germany
seen from United States
seen from Thailand

seen from United States

seen from United States
seen from United States
seen from United States

seen from Türkiye

seen from United States
seen from United States
seen from United States
seen from United States
seen from United States
seen from United States
@foxfamhvac
How I Troubleshoot an Air Conditioner 2-Stage Compressor (Solenoid)
This video will focus on troubleshooting the reversing valve on a heat pump, also known as the switchover valve. The reversing valve exists to change the di...
Probably one of the best technical videos I've done since I started making videos 5 years ago. I'm liking the way these videos are turning out. Let me know what you think. This week we're talking about the REVERSING VALVE on a HEAT PUMP.
What Happens During the Defrost Cycle on a Heat Pump? (You Can Do This!)
What Happens in Defrost Mode on a Heat Pump?
There’s something mystical when it comes to the heat pump system. We know it runs like a normal air conditioner in the cooling season, but when we get into heating season, some extra components come into play and we get confused or lose track of the sequence of operation for a heat pump.
So let’s go over some basics, that even I have to review from time to time, because heat pumps are not my strongest suit. I have a video called Basic Heat Pump Operation that you might want to refer to if you need an even more stripped-down version of heat pump operation. This one’s going to focus on the defrost function and what we should be checking to diagnose a heat pump that’s not working or might be frozen over in heating mode on a cold day.
So let’s quickly review some things we learned in the last video. In cooling mode, the heat pump works just like an air conditioner. The refrigerant cycles through the system and basically makes the indoor evaporator coil, a cold coil, and the outdoor unit's coil the hot coil. We remove the heat from inside the house at the outdoor unit, and pull it out to the outdoor coil to be released into the atmosphere.
In heating mode, a reversing valve reverses the flow of refrigerant to make the indoor coil the hot coil and the outdoor coil the cold coil. So, we're trying to extract heat from the outside and bring it inside, which can be done down to a certain outdoor temperature. After that, there is very little heat in the air to extract, so heat strips will kick in to supplement that effort.
A regular occurrence with a heat pump in the heating season is for the outdoor unit to go through a defrost cycle. You can imagine that cold outdoor coil interacting with the cold outdoor temperatures can cause some freezing. Anytime that outdoor coil gets below 40° or so, the outdoor coil being the cold coil develops frost on it. It can't keep operating this way, or that frost will develop into a straight-up ice block!
So, we want to melt this frost by essentially switching back into cooling mode. Because remember, in cooling mode, the outdoor coil becomes the hot coil. You’ll notice when you wire in the low voltage on a heat pump, you’re not just wiring in two wires like on a normal AC condenser. Single stage heat pumps need five wires running outside to them. Red for “24 volts”, Blue for “Common” which can be labeled B or C on defrost boards, Orange for the “Reversing Valve” or the O terminal, Yellow for “1st stage compressor” or the Y terminal, and something like a black or brown for the X2 terminal or “Emergency Heat.”
Notice I didn’t say “Y for cooling” because the same Y terminal is energized whether we’re in cooling or heating mode. We’re essentially energizing the compressor and fan on the outdoor unit. Whether we want to be in cooling or heating is up to the “O” terminal being energized or not.
Remember, these wires can be any color coming from the indoor air handler to the outdoor heat pump. All wires are copper inside. So, for the Y terminal at the heat pump defrost board, if a wire with purple sheathing leaves the Y terminal at the indoor air handler, then the other end of that purple wire should be tied into the Y terminal at the heat pump. It doesn’t matter what color that wire is.
The reason we have so many wires coming to the outdoor unit is to relay signals given from the heat pump to the air handler when it goes into defrost. The defrost board is the quarterback for this whole play too. For the defrost cycle to begin, two things have to happen. A sensor attached to the outdoor refrigerant coil (the copper coil)(or aluminum) has to get down to 26° F, and a second requirement is that the defrost board has to agree that the compressor has run the required amount of time. On the equipment I usually work on, it’s either 45 or 90 minutes.
When those two requirements have been met, a contact on the defrost board closes, completing a circuit to read 24 volts at X2 so the heat strips at the air handler will come on. Inside at the air handler, the fan still blows, which means there is cold air coming out of the ducts. But the air handler's heat strips come on to neutralize the cold air.
That same circuit closing causes the O terminal to have 24 volts which reverses the flow of refrigerant to cooling mode. You’ll hear when that happens too because the reversing valve makes a pretty noticeable whooshing sound when the change in directions happens. We explain more about the reversing valve in another video.
The third thing that happens when that circuit completes is a set of contacts open to stop the outdoor fan motor. This is to help warm the coils up faster. Because if we were drawing cold air across the outdoor coils when we were trying to warm them up, it would be counterproductive.
You would think the reversing valve would energize to go in to heating mode, but on 90% of the systems out there, not having 24 volts to the reversing valve causes the system to default to heating mode. In most parts of the country, having heat is more important than having cool air, so the reversing valve on a heat pump defaults to heating mode. Here in California during the summer, we would strongly debate that.
So, what have we done here and what terminals are supposed to be reading what voltage when defrost happens? You’ll see that: • 24 volts can be read between C an R on the defrost board. • 24 volts can be read between C and O. • 24 volts can be read between C and Y. • 24 volts can be read between C and X2 or whatever the emergency heat terminals happen to be labeled on your equipment.
• Also, the high voltage wires (usually labelled D1 and D2) on the defrost board leading to the outdoor fan motor, will only be sending 120 to the motor instead of 240. So, one of those terminals will have 120 to ground and the other will have 0 volts to ground.
What needs to happen for the demand defrost cycle to complete? When the liquid temperature leaving the outdoor coil reaches about 50 degrees, the defrost termination relay on the defrost board opens. If the temperature doesn’t rise to that point after 10 minutes, an override switch will open, and de-energize the relay which will terminate the cycle.
One last time the reversing valve makes a big whooshing sound and switches the flow of refrigerant back to heating mode, the outdoor fan turns on, the heat strips inside turn off, and the indoor coil becomes the hot coil again.
When defrost has completed and the system has gone back in to heating mode, here are the voltages you’ll read back at those same terminals from earlier.
• 24 volts can be read between C an R on the defrost board. • 0 volts can be read between C and O. • 24 volts can be read between C and Y. • 0 volts can be read between C and X2 or whatever the emergency heat terminals happen to be labeled on your equipment. • Also, the high voltage wires on the defrost board leading to the outdoor fan motor, will be reading 120 to ground on each terminal.
If you find that the outdoor heat pump is turning into a giant ice ball, there’s a few things to check before condemning the defrost board. After the system has been turned off a while and the ice has melted, let’s make sure the coils are clean. Restricted airflow across the indoor coil or the outdoor coil can cause the ice build up.
If the coils are clean, we need to check the refrigerant levels. If those are good, then something’s going wrong with the defrost operation. It could be the refrigerant line or ambient sensors, the actual board itself, or the reversing valve that is malfunctioning.
Most of the time the temperature sensors are permanently attached to the defrost board, so if they’re not reading correctly, the whole board would have to be replaced. Installation guides have tables that show the resistance the sensors should be reading at certain temperatures. Using your meter and some super thin leads will help you determine the readings.
Remember, the defrost board sends 24 volts to the reversing valve at the O terminal. Is that 24 volts reaching the solenoid on the reversing valve? No? Then check the wire connections. If they’re good. Then the defrost board itself is likely bad.
Yes, you do have 24 volts? Then something is going wrong with that solenoid and or the valve itself. But the defrost board is doing it’s job.
Just like with control boards on a furnace, if the board is giving the proper voltage to the motor and the motor isn’t working, it’s not the board. If the board isn’t giving the proper voltage, then it’s the board or something else upstream of it.
See! Defrost boards aren’t that hard, huh?
When it comes to heat pumps and air conditioners, they're actually very similar. Today I wanted to share my experience with heat pumps and focus on how they operate to give you cooling in the summer and heating in the winter.
Air Source Heat Pump Basics
Many new techs get intimidated when they work in an area with predominately gas/electric systems and have to work on a heat pump. The same goes for those who work on heat pumps a lot and then have to work on a gas furnace. It's foreign to those new techs, and they feel less confident working on those systems.
Today we're going to try and clarify those mysterious thoughts so you can better understand them.
So, if you didn't already know, in cooling mode, the heat pump works just like an air conditioner, in that a 24-volt signal comes to the outdoor contactor to turn that unit on. The contactor switch gets pulled in, which allows the 240 volts from one side of the contactor onto the other side so that voltage can make its way to a capacitor that supports the compressor and the condenser fan motor.
The refrigerant cycles through the system and basically makes the indoor evaporator coil, a cold coil, and the outdoor unit's coil the hot coil. At the evaporator coil, a fan blows across the cold coil and sends that cold air into the duct system and onto the rooms of the house. We remove the heat from inside the house at the outdoor unit and pull it out to the outdoor coil to be released into the atmosphere.
A heat pump just has a reversing valve that reverses the flow of refrigerant to make the indoor coil the hot coil and the outdoor coil the cold coil. So we're trying to extract heat from the outside and bring it inside, which can be done down to a certain outdoor temperature. After that, there is very little heat in the air to extract, so heat strips will kick in to supplement that effort.
Heat strips are a wire coil that is strung out across a rack and sits in the blower motor's airstream. They get so hot they glow orange. They're great, but they're expensive to run.
A regular occurrence with a heat pump in the heating season is for the outdoor unit to go through a defrost cycle. You can imagine the cold outdoor coil interacting with cold outdoor temperatures can cause some freezing. Anytime that outdoor coil gets below 32°, the outdoor being the cold coil develops frost on it. It can't keep operating this way, or frost will develop into a straight-up ice block!
A temperature sensor is mounted onto the outdoor coil to monitor this situation. When enough frost develops on the coil, a defrost board in the outdoor heat pump control panel will energize, sending it into a defrost cycle. Another sensor is included here. It's an ambient temperature sensor.
The difference between the ambient and the outdoor coil temperature is the difference or delta-T measurement. This delta-T measurement is what ultimately determines the need to go into defrost.
Defrost Cycle Only Works in Heating Mode
Now that the sensor on the outdoor coil has signaled to the defrost board it's time to go into defrost, a few things will happen. The defrost board is the quarterback for this whole play too. Because the outdoor coil was the cold coil and freezing up, we need something to melt that outdoor coil so it can function properly again. So the reversing valve lets out a big whooshing sound and reverses the flow of refrigerant so we can essentially go into air conditioning mode again and make the outdoor coil the hot coil. Also, at the outdoor unit, you'll notice the heat pump's fan motor stop running. This is to help warm the coils up faster. Because if we were drawing cold air across the outdoor coils when we were trying to warm them up, it would be counterproductive.
Inside at the air handler, the fan still blows, which means there is cold air coming out of the ducts. But the air handler's heat strips come on to neutralize the cold air. All this happens until the outdoor coils are warm enough to go back into heat mode and become the cold coil again—maybe 45 to 90 seconds.
One last time the reversing valve makes a big whooshing sound and switches the flow of refrigerant back to heating mode, the outdoor fan turns around on, the heat strips inside turn off, and the indoor coil becomes the hot coil again.
Whew!
Real quick, I wanted to mention that this method of defrost control is called "defrost on demand." Some older systems defrost cycle is called "electronic time-temperature defrost." Basically, defrost is started every 50, 70, or 90 minutes and has a sensor that tells it to go back to heating mode.
Let's get into some more details about the reversing valve and the defrost board in other blogs. For now, I just wanted to go over the sequence that happens for heating and cooling to work on the heat pump system. There are ways to test the reversing valve for diagnostic reasons. There are also ways you can force the unit into defrost when performing maintenance or a diagnostic call on a heat pump. Another test you can do is test the sensors to see if they are dialed in enough to make the right call to go into and come out of defrost.
Admiring #nature while #golfing. Between shots is a great time to look around at #ancilhoffman plenty of #wildlife to be seen (at Ancil Hoffman Golf Course) https://www.instagram.com/p/B1aTZPoFyFS/?igshid=cmqw2qz1folh
Installed another #trane #hvacsystem in #Sacramento this week. Love serving the downtown Sacramento area. Keeping it cool! https://www.instagram.com/p/B0Zo_RhlRmh/?igshid=2k04u9j2h1xt
Installed a #trane 18 Seer 2-stage heat pump for our customer Linda. So proud of our work done by @colinsballin13 and Erik Hayes. But seriously Trane, can these Tam9's get any bigger please. 24" inches wide isn't enough. 🤣🤣🛠️🛠️ (at Rancho Cordova, California) https://www.instagram.com/p/B0BLRrUlpcN/?igshid=nhkrxtun7mic
#txv another one bites the dust (at Sacramento, California) https://www.instagram.com/p/Bz3ajw9lWmB/?igshid=1dc8xnef2oyut
New #johnsoncontrols #evcon #407c AC installed today. Old Amana had a leak in the condenser coil... (at Rosemont, California) https://www.instagram.com/p/Bz3Z7LElVX4/?igshid=rj3qlcobcd62
Spliced on some new stat wire to the existing exposed wire today! Added some half inch flexible conduit to protect it better. This should prevent any low voltage shorts in the future! (at Southport, West Sacramento, California) https://www.instagram.com/p/BzlaOq2FFey/?igshid=3r46ovso5j6q
Loving the new Trane 34" furnace! #foxfamilyheatingandair (at Elk Grove, California) https://www.instagram.com/p/BzcDejIFhza/?igshid=4n6okvhwpkwc
#generalelectric classic furnace. Changing it out soon to a #trane (at Sacramento, California) https://www.instagram.com/p/BzLwPTCFg8B/?igshid=1fxt7w4xz6dsa
Changed the #capacitor but the #compressor is running hot on this 100 degree amp draw. (at Fox Family Heating and Air Conditioning, Inc.) https://www.instagram.com/foxfamhvac/p/BzHa3rdFxij/?igshid=1a10a9bays6aq
#appion hoses really get those microns low! (at Folsom, California) https://www.instagram.com/foxfamhvac/p/BzE4CtJlAKd/?igshid=1mod147dbh8q
Sophie's getting bigger! 66lbs https://www.instagram.com/foxfamhvac/p/ByeL3TEFyIU/?igshid=905s008jkyh2